Connecticut / Events /
Treatment plant bypass: SOUTH WINDSOR, Jun 21, 2026
Ended (as reported) · SOUTH WINDSOR (CT DEEP Performance Dashboard)
Source: SOUTH WINDSOR (CT DEEP Performance Dashboard) via CT DEEP CSO/SSO Performance Dashboard (QScend), record 10791, the source gives no report time, retrieved 2026-11-02 11:20 UTC · notice
Colours no water as of Nov 2, 2026, 6:56 AM EST: the windows on the methods page have passed, or the record has no time to count from.
A report is not a test of the water. See how statuses are worked out.
1. The reported outfall
Outfall reported by SOUTH WINDSOR: “Treatment Plant, 1 Vibert Rd, South Windsor, CT”. Location: no coordinates in the record or the outfall registry.
2. Waters named in the notice
The notice names: “CT River”. We place it on Connecticut River, CT. Matched by the name of the water in the source record.
3. Modeled downstream reach
No modeled reach for this record in this build.
Source: water outlines from OpenBoatLaunch and OpenStreetMap contributors (ODbL); outfalls from EPA ECHO and the state outfall layers; modeled reaches computed by DirtyWaterWatch from USGS NLDI, NHDPlus and the nearest USGS gauge (Jobson 1996); basemap OpenFreeMap and OpenMapTiles.
When: three different times
The time of the event, the time the source reported, published or updated it, and the time we fetched it are kept apart. Times are shown in New England time; the record keeps the original offsets.
- Started
- Ended
- Precision
- Known to the minute
- Reported to the source
- not given
- Published
- not given
- Source last updated
- not given
- We fetched it
What and how much
- Type
- Treatment plant bypass
- Status in the record
- Ended (as reported)
- Material
- “Fully treated raw sewage except disinfection”
- Volume
- 1,227 gal (not stated whether estimated or measured)
- Volume in the source's words
- “1227 gallons”
Advice
The record carries no advice text from SOUTH WINDSOR (CT DEEP Performance Dashboard).
- Advice window
- not stated in the record; the state's window on the methods page applies
- Basis
- not stated
Source and revisions
- Source
- CT DEEP CSO/SSO Performance Dashboard (QScend)
- Record id at the source
- 10791
- Original notice
- https://deepct.qscend.mygovcenter.com/cms/cms?id=1
- Revision of
- none (first record)
- Revised by
- no later revision
Every field of the record
event_id | ct-deep:10791 |
|---|---|
source_id | ct-deep |
source_record_id | 10791 |
parent_event_id | null |
event_type | plant_bypass |
status | ended |
discharger_id | ct-south-windsor |
discharger_name | SOUTH WINDSOR |
npdes_permit | null |
outfall_id | null |
outfall_name | Treatment Plant, 1 Vibert Rd, South Windsor, CT |
waterbody_text | CT River |
water_slugs | ["connecticut-river-ct"] |
water_match | name |
lat | null |
lon | null |
coord_source | null |
coord_precision_m | null |
started_at | 2026-06-21T21:30:00-04:00 |
ended_at | 2026-06-21T21:30:00-04:00 |
time_precision | minute |
reported_at | null |
published_at | null |
source_updated_at | null |
fetched_at | 2026-11-02T11:20:59Z |
material | Fully treated raw sewage except disinfection |
volume_gal | 1227 |
volume_text | 1227 gallons |
estimate_flag | unknown |
authority | SOUTH WINDSOR (CT DEEP Performance Dashboard) |
advice_text | null |
advice_window_hours | null |
advice_window_basis | null |
source_url | https://deepct.qscend.mygovcenter.com/cms/cms?id=1 |
parse_error | null |
fixture | false |
file | events/ct-deep~3A10791.json |
placement_note | null |
unplaced_reason | null |
set_aside | null |
superseded | null |
duplicate_of | null |
reach | null |
reach_band | null |
The source's record (raw)
{
"Reporting Utility": "SOUTH WINDSOR",
"Status": "Closed",
"Incident Type": "Sewage Bypass",
"Weather Conditions": "Dry",
"Date Bypass Began or was Discovered": "06/21/2026",
"Event Start Time": "09:30 PM",
"Location of Bypass": "Treatment Plant",
"Type of Bypass": "Fully treated raw sewage except disinfection",
"Cause of Bypass": "Other",
"Cause of Bypass Other Explanation": "During a self cleaning cycle our UVT recorded a UV dose below 30 for about 40 seconds, with a minimum of 29.92.",
"How was Incident Discovered": "Review SCADA trends.",
"Estimated Quantity or Rate of Discharge": "1227 gallons",
"How was estimated Quantity or Rate Determined": "2.65 MGD at the time. 2.65 MG/24/60/60*40",
"Reach Waterbody": "Yes",
"Request ID": "10791",
"Waterbody Name": "CT River",
"Date Bypass Ended": "06/21/2026",
"Event End Time": "09:30 PM",
"Final Quantity": "1227 gallons",
"How was Final Volume Determined": null,
"How incident was resolved": "When the self cleaning cycle was completed the UV dose returned to normal.",
"Municipality": "South Windsor",
"Address": "1 Vibert Rd, South Windsor, CT",
"_view": "SSO DATA VIEW"
} Source: SOUTH WINDSOR (CT DEEP Performance Dashboard) via CT DEEP CSO/SSO Performance Dashboard (QScend), record 10791, the source gives no report time, retrieved 2026-11-02 11:20 UTC · notice
Personal fields (names, emails, phone numbers of staff) are removed from raw records before they are stored.