Connecticut / Events /
Treatment plant bypass: SOUTH WINDSOR, Aug 27, 2026
Ended (as reported) · SOUTH WINDSOR (CT DEEP Performance Dashboard)
Source: SOUTH WINDSOR (CT DEEP Performance Dashboard) via CT DEEP CSO/SSO Performance Dashboard (QScend), record 11342, the source gives no report time, retrieved 2026-11-02 11:20 UTC · notice
Colours no water as of Nov 2, 2026, 6:56 AM EST: the windows on the methods page have passed, or the record has no time to count from.
A report is not a test of the water. See how statuses are worked out.
1. The reported outfall
Outfall reported by SOUTH WINDSOR: “Treatment Plant, 1 Vibert Rd, South Windsor, CT”. Location: no coordinates in the record or the outfall registry.
2. Waters named in the notice
The notice names: “CT River”. We place it on Connecticut River, CT. Matched by the name of the water in the source record.
3. Modeled downstream reach
No modeled reach for this record in this build.
Source: water outlines from OpenBoatLaunch and OpenStreetMap contributors (ODbL); outfalls from EPA ECHO and the state outfall layers; modeled reaches computed by DirtyWaterWatch from USGS NLDI, NHDPlus and the nearest USGS gauge (Jobson 1996); basemap OpenFreeMap and OpenMapTiles.
When: three different times
The time of the event, the time the source reported, published or updated it, and the time we fetched it are kept apart. Times are shown in New England time; the record keeps the original offsets.
- Started
- Ended
- Precision
- Known to the minute
- Reported to the source
- not given
- Published
- not given
- Source last updated
- not given
- We fetched it
What and how much
- Type
- Treatment plant bypass
- Status in the record
- Ended (as reported)
- Material
- “Fully treated raw sewage except disinfection”
- Volume
- 8,333 gal (not stated whether estimated or measured)
- Volume in the source's words
- “8,333 gallons”
Advice
The record carries no advice text from SOUTH WINDSOR (CT DEEP Performance Dashboard).
- Advice window
- not stated in the record; the state's window on the methods page applies
- Basis
- not stated
What it does to the map, over time
- Advisory in effect Connecticut River: Discharge in progress, Aug 27, 2026, 8:30 AM EDT to Aug 27, 2026, 8:45 AM EDT
- Advisory in effect Connecticut River: Within the authority's advice window after the discharge ended, Aug 27, 2026, 8:45 AM EDT to Aug 29, 2026, 8:45 AM EDT
- Caution Connecticut River: Within the site's caution window after the discharge ended (data/rules.json), Aug 29, 2026, 8:45 AM EDT to Aug 30, 2026, 8:45 AM EDT
Source: intervals computed by DirtyWaterWatch (build/status.py) from this record and the rules on the methods page, as of 2026-11-02 11:56 UTC.
Source and revisions
- Source
- CT DEEP CSO/SSO Performance Dashboard (QScend)
- Record id at the source
- 11342
- Original notice
- https://deepct.qscend.mygovcenter.com/cms/cms?id=1
- Revision of
- none (first record)
- Revised by
- no later revision
Every field of the record
event_id | ct-deep:11342 |
|---|---|
source_id | ct-deep |
source_record_id | 11342 |
parent_event_id | null |
event_type | plant_bypass |
status | ended |
discharger_id | ct-south-windsor |
discharger_name | SOUTH WINDSOR |
npdes_permit | null |
outfall_id | null |
outfall_name | Treatment Plant, 1 Vibert Rd, South Windsor, CT |
waterbody_text | CT River |
water_slugs | ["connecticut-river-ct"] |
water_match | name |
lat | null |
lon | null |
coord_source | null |
coord_precision_m | null |
started_at | 2026-08-27T08:30:00-04:00 |
ended_at | 2026-08-27T08:45:00-04:00 |
time_precision | minute |
reported_at | null |
published_at | null |
source_updated_at | null |
fetched_at | 2026-11-02T11:20:59Z |
material | Fully treated raw sewage except disinfection |
volume_gal | 8333 |
volume_text | 8,333 gallons |
estimate_flag | unknown |
authority | SOUTH WINDSOR (CT DEEP Performance Dashboard) |
advice_text | null |
advice_window_hours | null |
advice_window_basis | null |
source_url | https://deepct.qscend.mygovcenter.com/cms/cms?id=1 |
parse_error | null |
fixture | false |
file | events/ct-deep~3A11342.json |
placement_note | null |
unplaced_reason | null |
set_aside | null |
superseded | null |
duplicate_of | null |
reach | null |
reach_band | null |
The source's record (raw)
{
"Reporting Utility": "SOUTH WINDSOR",
"Status": "Closed",
"Incident Type": "Sewage Bypass",
"Weather Conditions": "Dry",
"Date Bypass Began or was Discovered": "08/27/2026",
"Event Start Time": "08:30 AM",
"Location of Bypass": "Treatment Plant",
"Type of Bypass": "Fully treated raw sewage except disinfection",
"Cause of Bypass": "Electrical Equipment Failure",
"Cause of Bypass Other Explanation": "Loss of power during mainteneance to level snesor in UV chamber. Caused the UV system to go into a \"Limp\" mode where only the bottom two of 12 rows of bulbs were activated despite putting it in a manual overide mode. There was only partial disinfection ",
"How was Incident Discovered": "The electrical issues were noticed imediately but the affect on the disinfection weren't realized until about 9:30.",
"Estimated Quantity or Rate of Discharge": "8333 gallons",
"How was estimated Quantity or Rate Determined": "Flow at time of discharge was 1.6 MGD. 1600000 gpd / 24 hours/60 minutes*10 minutes=11,111 gallons *.75",
"Reach Waterbody": "Yes",
"Request ID": "11342",
"Waterbody Name": "CT River",
"Date Bypass Ended": "08/27/2026",
"Event End Time": "08:45 AM",
"Final Quantity": "8,333 gallons",
"How was Final Volume Determined": null,
"How incident was resolved": "We will need to contact the manufacturer to get this power seperated so we can safely lock out the bank without losing power to this critical sensor and cooling pumps. Additionally we should have away to overide this \"Limp\" mode. In the meantime we hold o",
"Municipality": "South Windsor",
"Address": "1 Vibert Rd, South Windsor, CT",
"_view": "SSO DATA VIEW"
} Source: SOUTH WINDSOR (CT DEEP Performance Dashboard) via CT DEEP CSO/SSO Performance Dashboard (QScend), record 11342, the source gives no report time, retrieved 2026-11-02 11:20 UTC · notice
Personal fields (names, emails, phone numbers of staff) are removed from raw records before they are stored.