Sanitary sewer overflow (SSO) reported — Oconee Joint Regional Sewer Authority, Oct 5, 2026
Ended (as reported) · South Carolina DES (ePermitting wastewater overflow list)
Source: South Carolina DES (ePermitting wastewater overflow list) via SC DES ePermitting wastewater overflow list (sanitary sewer overflow reports), record -7120597659561068290-2, reported Oct 9, 2026, 11:22 AM EDT, retrieved 2026-11-26 01:41 UTC · Read the original notice
Current status from this report
This report does not set a map status as of Nov 25, 2026, 8:59 PM EST. Check its dates and the status rules.
A report is not a test of the water. See how we assign statuses.
Read the original notice · Report an error
1. Reported wastewater outlet
Operator named in the record: Oconee Joint Regional Sewer Authority (federal wastewater discharge permit, NPDES, SC0033553). Outlet: “Manhole”. Location: not given in the report or in the outlet records.
Outfall: a pipe or outlet where wastewater enters a water body.
2. Waters named in the notice
The notice names: “Speeds Creek”. DirtyWaterWatch links this report to Speeds Creek, SC. Match basis: the water named in the report.
3. Estimated stretch
No downstream estimate is available for this report.
Zoom in to see waters with no current status.
Map sources
Water outlines and launches from OpenBoatLaunch and OpenStreetMap contributors (Open Database License); wastewater outlets from EPA and state records; downstream estimates by DirtyWaterWatch using U.S. Geological Survey maps and flow data. Base map: OpenFreeMap and OpenMapTiles.
What the source reports
Event and notice times use Eastern Time (EST or EDT). Retrieval times use Coordinated Universal Time (UTC).
When
- Started
- Ended
- Detail of the times
- Times known to the minute
What
- Type
- Sanitary sewer overflow (SSO): sewage spills from a sewer meant to carry sewage separately from rainwater.
- Status in the record
- Ended (as reported)
- Material
- not stated
- Cause
- “Electrical issue caused transducer switch that monitors wet well to fail. The pumps faulted out do to an incorrect timer setting and possible power failure during event.”
How much
- Volume
- “500 gallons” (1,893 litres, our conversion)
Advice in the source
This report includes no advice. Check current local health notices.
- Advice period
- This report does not state a period. See the rule DirtyWaterWatch applies and its source.
- Basis
- not stated
Who reported it
- Operator named
- Oconee Joint Regional Sewer Authority
- Authority
- South Carolina DES (ePermitting wastewater overflow list)
- Published by
- SC DES ePermitting wastewater overflow list (sanitary sewer overflow reports)
When it was reported and read
- Reported to the source
- Published
- not given
- Source last updated
- not given
DirtyWaterWatch observations
- Last retrieved by DirtyWaterWatch
Status history from this report
- Discharge or advisory reported Speeds Creek: Discharge reported ongoing, Oct 5, 2026, 9:30 PM EDT to Oct 20, 2026, 9:40 PM EDT
- Caution Speeds Creek: Within the caution period after the reported end, Oct 20, 2026, 9:40 PM EDT to Oct 23, 2026, 9:40 PM EDT
Source: DirtyWaterWatch calculations using this report and the published status rules. Updated 2026-11-26 01:59 UTC.
Source
- Source
- SC DES ePermitting wastewater overflow list (sanitary sewer overflow reports)
- Source record number
- -7120597659561068290-2
- Original notice
- Read the original notice
Record details
| Record identifier | sc-des-overflow-list:-7120597659561068290-2 |
|---|---|
| Source identifier | sc-des-overflow-list |
| Source record number | -7120597659561068290-2 |
| Earlier version | Not provided |
| Type | Sanitary sewer overflow (SSO) |
| Status in the report | Ended (as reported) |
| Sewer operator identifier | sc-ojrsa |
| Sewer operator | Oconee Joint Regional Sewer Authority |
| Federal wastewater discharge permit (NPDES) | SC0033553 |
| Outlet number | Not provided |
| Outlet name | Manhole |
| Water named in the report | Speeds Creek |
| Linked waters | speeds-creek-sc |
| How this report was linked to the water | the water named in the report |
| Latitude | Not provided |
| Longitude | Not provided |
| Location source | Not provided |
| Location accuracy | Not provided |
| Started | Oct 5, 2026, 9:30 PM EDT (2026-10-05T21:30:00-04:00) |
| Ended | Oct 20, 2026, 9:40 PM EDT (2026-10-20T21:40:00-04:00) |
| Detail provided by the source | to the minute |
| Reported to the source | Oct 9, 2026, 11:22 AM EDT (2026-10-09T11:22:46-04:00) |
| Published | Not provided |
| Source last updated | Not provided |
| Last retrieved by DirtyWaterWatch | Nov 25, 2026, 8:41 PM EST (2026-11-26T01:41:29Z) |
| Material | Not provided |
| Volume | 500 gallons (1,890 litres) |
| Volume as reported | 500 gallons |
| How volume was determined | not stated whether estimated or measured |
| Authority | South Carolina DES (ePermitting wastewater overflow list) |
| Advice | Not provided |
| Advice period, in hours | Not provided |
| Basis of the advice period | Not provided |
| Original notice | https://epermitting.des.sc.gov/ext/ncore/ss/ssolist?queryParams=%7B%22filter%22%3A%5B%7B%22submissionId%22%3A%22-7120597659561068290%22%7D%5D%2C%22top%22%3A50%7D |
Original source data
{
"id": "-6292562825224167226",
"actionTaken": "Changes were made to the timer to correct time settings according to the electrical plans. Other improvements were made to allow backup wet well float system to trigger alarm sooner.",
"actionToBeTaken": "Diverted wastewater flow to Martin Creek Pump Station emergency storage tank while issue was addressed.",
"agencyComments": null,
"countyDescription": "Oconee",
"countyId": "37",
"deqActions": null,
"dischargeDescription": "Electrical issue caused transducer switch that monitors wet well to fail. The pumps faulted out do to an incorrect timer setting and possible power failure during event.",
"dischargeQuality": "",
"dischargeType": "SSO Discharge",
"dischargeVolume": "500 gallons",
"dischargeVolumeNumeric": 500,
"eventEndDate": "2026-10-20T21:40:00.0000000-04:00",
"eventStartDate": "2026-10-05T21:30:00.0000000-04:00",
"featureDescription": "Manhole",
"featureNumber": null,
"landImpacted": null,
"locationDescription": "Manholes SPS-001 and SPS-002 directly adjacent to Speeds Creek Pump Station",
"permitNumber": "SC0033553",
"precipitationAmount": null,
"precipitationType": null,
"receivingWater": "Speeds Creek",
"reportStatusDescription": "Completed",
"reportStatusId": "COMPLETE",
"responsiblePartyName": "OCONEE JOINT REGIONAL SEWER AUTHORITY",
"sectionNumber": 2,
"siteName": "OJRSA CONEROSS CREEK WWTP",
"socRequirements": null,
"submissionId": "-7120597659561068290",
"submissionReceivedDate": "2026-10-09T11:22:46.6000000-04:00",
"submissionReferenceNumber": "HQS-62XE-9VBV8",
"state": "SC",
"county": "Oconee",
"reached_water": true
} Staff names, email addresses and phone numbers are removed from source data before it is stored.