Sanitary sewer overflow (SSO) reported — Monterey City, Nov 16, 2026

Ended (as reported) · California State Water Resources Control Board (CIWQS Sanitary Sewer System Database)

Source: California State Water Resources Control Board (CIWQS Sanitary Sewer System Database) via State Water Board CIWQS Sanitary Sewer System spill data: Cat1-2-3-Spills.txt (nightly flat file), record 909041, reported Nov 17, 2026, 8:16 AM PST, retrieved 2026-11-25 15:27 UTC · Read the original notice

Current status from this report

This report does not set a map status as of Nov 25, 2026, 5:59 PM PST. Check its dates and the status rules.

A report is not a test of the water. See how we assign statuses.

Read the original notice · Report an error

1. Reported wastewater outlet

Operator named in the record: Monterey City (federal wastewater discharge permit, NPDES, 3SSO11524). Outlet: “Del Monte Beach”. Location: 36.60379, -121.87161; location source: given in the source record.

Outfall: a pipe or outlet where wastewater enters a water body.

2. Waters named in the notice

The notice names: “Pacific Ocean”. DirtyWaterWatch links this report to Pacific Ocean, CA. Match basis: the water named in the report.

3. Estimated stretch

This report's estimated stretch has no current status. We drew the estimated stretch along the shore from the place the report names to our distance limit of 12 miles (20 km) in each direction. This estimates water movement, not bacteria levels.

Map sources

Water outlines and launches from OpenBoatLaunch and OpenStreetMap contributors (Open Database License); wastewater outlets from EPA and state records; downstream estimates by DirtyWaterWatch using U.S. Geological Survey maps and flow data. Base map: OpenFreeMap and OpenMapTiles.

Open on the main map

What the source reports

Event and notice times use Pacific Time (PST or PDT). Retrieval times use Coordinated Universal Time (UTC).

When

Started
Ended
(the report is not yet certified (CIWQS status Draft Submitted); the end is the one the operator gave and may change at certification)
Detail of the times
Times known to the minute

What

Type
Sanitary sewer overflow (SSO): sewage spills from a sewer meant to carry sewage separately from rainwater.
Kind of record
“Category 1 Spill”
Status in the record
Ended (as reported)
Material
“untreated sewage”
Cause
“Natural Disaster (specify below)”
Where it came out
“Gravity Mainline”

How much

Volume
“11,250 gallons spilled (estimated total leaving the sewer system); 11,250 gallons reached surface water; 0 gallons recovered”, estimated (42,586 litres, our conversion)
Reached the water
11,250 gallons

Advice in the source

This report includes no advice. Check current local health notices.

Advice period
This report does not state a period. See the rule DirtyWaterWatch applies and its source.
Basis
not stated

Who reported it

Operator named
Monterey City
Authority
California State Water Resources Control Board (CIWQS Sanitary Sewer System Database)
Published by
State Water Board CIWQS Sanitary Sewer System spill data: Cat1-2-3-Spills.txt (nightly flat file)

When it was reported and read

Reported to the source
Published
not given
Source last updated

DirtyWaterWatch observations

Last retrieved by DirtyWaterWatch

Status history from this report

Source: DirtyWaterWatch calculations using this report and the published status rules. Updated 2026-11-26 01:59 UTC.

Source

Source
State Water Board CIWQS Sanitary Sewer System spill data: Cat1-2-3-Spills.txt (nightly flat file)
Source record number
909041
Original notice
Read the original notice

Record details

Record details
Record identifierca-swrcb-ciwqs-spills-flatfile:909041
Source identifierca-swrcb-ciwqs-spills-flatfile
Source record number909041
Earlier versionNot provided
TypeSanitary sewer overflow (SSO)
Status in the reportEnded (as reported)
Sewer operator identifierca-monterey
Sewer operatorMonterey City
Federal wastewater discharge permit (NPDES)3SSO11524
Outlet numberNot provided
Outlet nameDel Monte Beach
Water named in the reportPacific Ocean
Linked waterspacific-ocean-ca
How this report was linked to the waterthe water named in the report
Latitude36.604
Longitude-121.872
Location sourcegiven in the source record
Location accuracyNot provided
StartedNov 16, 2026, 4:36 PM PST (2026-11-16T16:36:00-08:00)
EndedNov 17, 2026, 4:00 PM PST (2026-11-17T16:00:00-08:00)
Detail provided by the sourceto the minute
Reported to the sourceNov 17, 2026, 8:16 AM PST (2026-11-17T08:16:00-08:00)
PublishedNot provided
Source last updatedNov 19, 2026, 12:00 AM PST (2026-11-19)
Last retrieved by DirtyWaterWatchNov 25, 2026, 7:27 AM PST (2026-11-25T15:27:01Z)
Materialuntreated sewage
Volume11,250 gallons (42,600 litres)
Volume as reported11,250 gallons spilled (estimated total leaving the sewer system); 11,250 gallons reached surface water; 0 gallons recovered
How volume was determinedestimated
AuthorityCalifornia State Water Resources Control Board (CIWQS Sanitary Sewer System Database)
AdviceNot provided
Advice period, in hoursNot provided
Basis of the advice periodNot provided
Original noticehttps://www.waterboards.ca.gov/water_issues/programs/sso/docs/data_files/Cat1-2-3-Spills.txt

Original source data

{
  "region": "3",
  "wdid": "3SSO11524",
  "enrollee_status": "Active",
  "system_name": "Monterey City CS",
  "agency_name": "Monterey City",
  "spill_event_id": "909041",
  "version": "1.1",
  "spill_status": "Draft Submitted",
  "CERTIFIED_BY": null,
  "CERTIFIER_TITLE": null,
  "draft_submitted_on": "19-NOV-26",
  "first_certified_on": null,
  "final_certified_on": null,
  "spill_type": "Category 1 Spill",
  "location_name": "Del Monte Beach",
  "enrollee_notified_at": "11/17/2026 07:30",
  "crew_arrival_at": "11/17/2026 08:15",
  "start_at": "11/16/2026 16:36",
  "caloes_notified_at": "11/17/2026 08:16",
  "caloes_control_number": "26-5939",
  "technical_report_on": null,
  "DESCRIPTION_PHOTOGRAPHS_AND_GPS_COORDINATES_OF_THE_SYSTEM_LOCATION_WHERE_THE_SPILL_ORIGINATED": "15 inch VCP pipe from Del Monte Beach Neighborhood to Monterey lift station exposed in Sand dune approximate 30 feet of pipe collapsed from high surf.",
  "lat": "36.60379",
  "lon": "-121.87161",
  "appearance_points": "Gravity Mainline",
  "IF_OTHER_APPEARANCE_POINT_DESCRIBE": null,
  "ADDITIONAL_SPILL_APPEARANCE_POINT(S)_EXPLANATION": null,
  "volume_total_gal": "11250",
  "DESCRIPTION_AND_PHOTOGRAPHS_OF_SPILL_EXTENT_AND_SPILL_BOUNDARIES": "Spilled directly into surface waters",
  "reached_drainage_system": "N",
  "DESCRIPTION_OF_THE_DRAINAGE_CONVEYANCE_SYSTEM_TRANSPORTING_THE_SPILL_AND_SYSTEM_ENTRY_LOCATION(S)": null,
  "volume_recovered_from_drainage_gal": null,
  "volume_left_in_drainage_gal": null,
  "DESCRIPTION_AND_PHOTOGRAPHS_OF_ALL_DISCHARGE_POINT(S)_INTO_THE_SURFACE_WATER": "15-inch sewer main runs along the sand dune adjacent to the ocean. A 30-foot section of pipe collapsed. Discharge is approximately 50 feet from the surf zone. Spill discharged directly to the ocean.",
  "volume_to_surface_water_gal": "11250",
  "volume_recovered_gal": "0",
  "destinations": "Surface Water",
  "IF_OTHER_SPILL_DESTINATION_DESCRIBE": null,
  "DESCRIPTION_OF_THE_SPILL_EVENT_DESTINATION(S)": "15-inch sewer main runs along the sand dune adjacent to the ocean. A 30-foot section of pipe collapsed. Discharge is approximately 50 feet from the surf zone. Spill discharged directly to the ocean.",
  "destination_points_given": "Y",
  "end_at": "11/17/2026 16:00",
  "DESCRIPTION_OF_SPILL_VOLUME_ESTIMATIONS_CALCULATIONS": "Used a diurnal peaking factor with peak flows between 6am and 9am observed at 10gpm with a peaking factor of 1.6. Overnight and afternoon flows have a peaking factor of .6 or 6gpm. Calculated the average nominal flow to be 6.25gpm x 30 hrs x 60 = 11250",
  "DESCRIPTION_OF_THE_METHODOLOGY(IES)_FOR_ESTIMATIONS_OF_SPILL_START_AND_END_TIME": "Using a diurnal flow diagram with the following peaking factors and observations: 12am 0.7PF = 4.4gpm 3am 0.8PF = 5 gpm 6am 1.6PF = 10gpm 8am 1.6PF = 10gpm (observed) 12pm 0.7PF = 4gpm 3pm 0.7PF = 8.75gpm 7pm 1.4PF = 8.75gpm 10pm 0.7PF = 4.4gpm",
  "causes": "Natural Disaster (specify below)",
  "IF_OTHER_CAUSE_DESCRIBE": "Heavy surf conditions, combined with a king tide event, eroded sand dune and exposed the 15 VCP sewer main. As the sand dune receded, the pipe collapsed and rolled into the ocean.",
  "failure_location": "Gravity Mainline",
  "IF_OTHER_FAILURE_LOCATION_DESCRIBE": null,
  "DESCRIPTION_OF_THE_PIPE_MATERIAL_AT_THE_FAILURE_LOCATION": "Vitrified Clay",
  "IF_OTHER_PIPE_MATERIAL_DESCRIBE": null,
  "ESTIMATED_AGE_OF_PIPE_MATERIAL_AT_THE_FAILURE_LOCATION": "80",
  "DESCRIPTION_OF_THE_IMPACT_OF_THE_SPILL": "Del Monte Beach will be closed for 72 hours from the end of the spill event. There is a short-term nearshore potential for illness if the beach closure is disregarded. Broad ecological impact on Monterey Bay and the Pacific Ocean would be limited by rapid dilution.",
  "storm_event": "Y",
  "SPILL_RESPONSE_ACTIVITIES": "Mitigated Effects of Spill (specify below); Restored Flow",
  "IF_OTHER_RESPONSE_ACTIVITY_DESCRIBE": null,
  "DESCRIPTION_OF_SPILL_RESPONSE_ACTIVITIES": "The City of Monterey established a temporary bypass using 12-inch HDPE pipe to sleeve the 15-inch main and span the 30 FT of collapsed VCP. An excavator was used to rake sand toward the dune to bridge the suspended pipe. There was no solids or liquid that could be retrieved as the surf zone washed everything into the ocean.",
  "SPILL_CORRECTIVE_ACTION": "Other (specify below)",
  "IF_OTHER_CORRECTIVE_ACTION_DESCRIBE": null,
  "DESCRIPTION_OF_SPILL_CORRECTIVE_ACTION": "The City of Monterey established a temporary bypass using 12-inch HDPE pipe to sleeve the 15-inch main and span the 30 FT of collapsed VCP. An excavator was used to rake sand toward the dune to bridge the suspended pipe. This pipe has been watched closely for several years as the dunes have been visibly receding from coastal erosion. There is a grant awarded from OPC to relocate this line, which is currently in early design phase.",
  "SCHEDULE_OF_MAJOR_MILESTONES": "There is a grant awarded from OPC to relocate this line, which is currently in the early design phase.",
  "response_completed_at": "11/17/2026 16:00",
  "DETAILED_NARRATIVE_OF_INVESTIGATION_AND_INVESTIGATION_FINDINGS_OF_CAUSE_OF_SPILL": "Heavy surf conditions, combined with a king tide event, eroded sand dune and exposed the 15 VCP sewer main. As the sand dune receded, the pipe collapsed and rolled into the ocean",
  "IS_THE_ENROLLEE_CONDUCTING_AN_ONGOING_INVESTIGATION_(YES_NO)?": "N",
  "REASONS_FOR_AN_ONGOING_INVESTIGATION": null,
  "EXPECTED_DATE_OF_COMPLETION_OF_INVESTIGATION": null,
  "receiving_water": "Pacific Ocean",
  "receiving_water_type": "Ocean",
  "IF_OTHER_RECEIVING_WATER_DESCRIBE": null,
  "DESCRIPTION_OF_THE_WATER_BODY(S)": "Monterey Bay - Pacific Ocean",
  "OBSERVED_IMPACTS_ON_AQUATIC_LIFE": "No observed impacts.",
  "public_access_impact": "Public Closure",
  "IF_OTHER_PUBLIC_ACCESS_IMPACT_DESCRIBE": null,
  "closing_entity": "City of Monterey",
  "days_closed_or_restricted": "3",
  "within_1000_ft_of_intake": "N",
  "samples_collected": "Y",
  "IDENTIFY_SAMPLE_LOCATIONS": "Sampling is being done by Monterey County Health Department",
  "IDENTIFY_PARAMETERS_THE_WATER_QUALITY_SAMPLES_WERE_ANALYZED_FOR": "Sampling is being done by Monterey County Health Department",
  "LOCAL_REGULATORY_ENFORCEMENT_ACTION_TAKEN": null,
  "IDENTIFIED MODIFICATIONS PREVENT SPILL OCCURRENCES": null,
  "ADJUSTED_SCHEDULE/METHOD_OF_PREVENTIVE_MAINTENANCE": null,
  "PLANNED_REHABILITATION_OR_REPLACEMENT_OF_SANITARY_SEWER_ASSET": null,
  "INSPECTED_REPAIRED_ASSET(S)_OR_REPLACED_DEFECTIVE_ASSET(S)": null,
  "CAPITAL_IMPROVEMENTS": null,
  "DOCUMENTATION_VERIFYING_IMMEDIATELY_IMPLEMENTED_SYSTEM_MODIFICATIONS_AND_OPERATING/MAINTENANCE_MODIFICATIONS": null,
  "DESCRIPTION_OF_SPILL_RESPONSE_ACTIVITIES_MODIFICATIONS": null,
  "ONGOING_INVESTIGATION_EFFORTS": null,
  "spill_category": "1",
  "reached_water": true,
  "destination_points": [
    {
      "lat": 36.60388,
      "lon": -121.87159
    }
  ]
}

Staff names, email addresses and phone numbers are removed from source data before it is stored.