DirtyWaterWatch Public waters. Public record.

Florida / Reports /

Sanitary sewer overflow (SSO) reported — City of Naples Water Reclamation Facility, Oct 7, 2026

Ended (as reported) · Florida Department of Environmental Protection (Public Notice of Pollution)

Source: Florida Department of Environmental Protection (Public Notice of Pollution) via Florida DEP Public Notice of Pollution, sewage and wastewater notices (PNP feature service), record 20269950-20261007T224853, reported Oct 7, 2026, 10:48 PM EDT, retrieved 2026-11-05 06:08 UTC · Read the original notice

Current status from this report

Earlier version. A later record from the same source replaces this one. The newest version sets the map status. read the newer version

A report is not a test of the water. See how we assign statuses.

Read the original notice · Report an error

1. Reported wastewater outlet

Operator named in the record: City of Naples Water Reclamation Facility. Outlet: “1400 3rd Ave N Raw Feed Line Break”. Location: 26.15156, -81.78782; location source: given in the source record, accurate to about 15 metres.

Outfall: a pipe or outlet where wastewater enters a water body.

2. Waters named in the notice

The notice names: “Gordon River”. DirtyWaterWatch links this report to Gordon River, FL. Match basis: the water named in the report.

3. Estimated downstream stretch

No downstream estimate is available for this report.

Map sources: water outlines and launches from OpenBoatLaunch and OpenStreetMap contributors (Open Database License); wastewater outlets from EPA and state records; downstream estimates by DirtyWaterWatch using U.S. Geological Survey maps and flow data. Base map: OpenFreeMap and OpenMapTiles.

Open on the main map

When it happened and when it was reported

Event and notice times use Eastern Time (EST or EDT). Retrieval times use Coordinated Universal Time (UTC).

Started
Ended
Detail provided by the source
Times known to the day only
Reported to the source
Published
not given
Source last updated
not given
Last retrieved by DirtyWaterWatch

What and how much

Type
Sanitary sewer overflow (SSO): sewage spills from a sewer meant to carry sewage separately from rainwater.
Status in the record
Ended (as reported)
Material
“untreated wastewater”
Volume
330,000 gallons (estimated)
Volume as reported
“330,000 gallons”

Advice from Florida Department of Environmental Protection (Public Notice of Pollution)

This report includes no advice. Check current local health notices.

Advice period
This report does not state a period. See the rule DirtyWaterWatch applies and its source.
Basis
not stated

Source and versions

Source
Florida DEP Public Notice of Pollution, sewage and wastewater notices (PNP feature service)
Source record number
20269950-20261007T224853
Original notice
Read the original notice
Earlier version
None: this is the first record
Later versions
version 2

Record details

Record details
Record identifierfl-dep-pnp:20269950-20261007T224853
Source identifierfl-dep-pnp
Source record number20269950-20261007T224853
Earlier versionNot provided
TypeSanitary sewer overflow (SSO)
Status in the reportEnded (as reported)
Sewer operator identifierNot provided
Sewer operatorCity of Naples Water Reclamation Facility
Federal wastewater discharge permit (NPDES)Not provided
Outlet numberNot provided
Outlet name1400 3rd Ave N Raw Feed Line Break
Water named in the reportGordon River
Linked watersgordon-river-fl
How this report was linked to the waterthe water named in the report
Latitude26.152
Longitude-81.788
Location sourcegiven in the source record
Location accuracy, in metres15
StartedOct 7, 2026 (2026-10-07T00:00:00-04:00)
EndedOct 7, 2026 (2026-10-07T00:00:00-04:00)
Detail provided by the sourceto the day only
Reported to the sourceOct 7, 2026 (2026-10-07T22:48:53-04:00)
PublishedNot provided
Source last updatedNot provided
Last retrieved by DirtyWaterWatchNov 5, 2026, 1:08 AM EST (2026-11-05T06:08:44Z)
Materialuntreated wastewater
Volume, in gallons330,000
Volume as reported330,000 gallons
How volume was determinedestimated
AuthorityFlorida Department of Environmental Protection (Public Notice of Pollution)
AdviceNot provided
Advice period, in hoursNot provided
Basis of the advice periodNot provided
Original noticehttps://ags.dep.state.fl.us/arcgis/rest/services/External_Services/PNP/FeatureServer/1/query?where=INCIDENT_NUMBER%3D20269950&outFields=INCIDENT_NUMBER,INCIDENT_NAME,INCIDENT_REPORT,DATE_TIME_OF_REPORT,RELEASE_START_DATE_TIME,RELEASE_ONGOING,RELEASE_END_DATE_TIME,FACILITY_NAME,FACILITY_ADDRESS_LINE_1,FACILITY_ADDRESS_LINE_2,FACILITY_CITY,FACILITY_STATE,FACILITY_ZIP5,AFFECTED_COUNTIES,MIGRATED_OFFSITE,MIGRATED_COUNTIES,LATITUDE,LONGITUDE,DATUM,MAP_SOURCE_SCALE,OBJECTID&returnGeometry=false&f=json

Original source data

{
  "INCIDENT_NUMBER": 20269950,
  "INCIDENT_NAME": "1400 3rd Ave N Raw Feed Line Break",
  "INCIDENT_REPORT": "Incident Description: On October 7, 2026, a raw wastewater release occurred at the City of Naples Water Reclamation Facility, 1400 3rd Avenue North, Naples, FL 34102 16:45: Release began from the 30-inch raw feed line. Preliminary findings indicate failure of a 2-inch direct tap. 16:52: The operator on duty notified utility management. 17:00 to 17:30: City personnel coordinated the response, and utility management arrived onsite. 17:51: East and West Influent lines were closed, and the spill ceased. The estimated release volume is 330,000 gallons, based on SCADA flow data from 16:45 to 17:51. 18:00: Emergency contractors arrived onsite. The City selected QE for emergency repairs and Earthview for vacuum-truck support at city lift stations and spill recovery. A containment dike was constructed, and City vacuum trucks were deployed to remove wastewater from the plants stormwater swales and ponds. 19:00 to 20:00: Laboratory personnel collected samples at two water-body entry points and two samples from the plant's stormwater ponds. An estimated 1,000 gallons entered Gordon River. The majority of the spill volume was contained onsite within the facilitys stormwater system, consisting of several swales and two ponds. City vacuum trucks have recovered approximately 20,000 gallons from this system to date; with further recovery efforts ongoing. Current status: The spill has ceased. Recovery efforts continue, State watch office has been notified, and emergency repair of the raw feed line remains in progress through contractor QE. Wastewater Type: Untreated Cause: Break-in-Line Spill Volume: 330,000 Volume Recovered: 20,000 Waterbodies Impacted: Y Clean-up Status: In-progress Clean-up Actions: Vacuumed/pump truck, Washed down area, Water samples taken, Raked and disposed of debris Agencies Notified: [removed]",
  "DATE_TIME_OF_REPORT": 1791413333000,
  "RELEASE_START_DATE_TIME": 1791331200000,
  "RELEASE_ONGOING": "N",
  "RELEASE_END_DATE_TIME": 1791331200000,
  "FACILITY_NAME": "City of Naples Water Reclamation Facility",
  "FACILITY_ADDRESS_LINE_1": "1400 3rd Ave N",
  "FACILITY_ADDRESS_LINE_2": null,
  "FACILITY_CITY": "Naples",
  "FACILITY_STATE": "FL",
  "FACILITY_ZIP5": 34102,
  "AFFECTED_COUNTIES": "Collier",
  "MIGRATED_OFFSITE": "Y",
  "MIGRATED_COUNTIES": "Collier",
  "LATITUDE": 26.151559,
  "LONGITUDE": -81.787825,
  "DATUM": "WGS84",
  "MAP_SOURCE_SCALE": null,
  "reached_water": true
}

Staff names, email addresses and phone numbers are removed from source data before it is stored.