Sanitary sewer overflow (SSO) reported — City of Naples Water Reclamation Facility, Oct 7, 2026
Ended (as reported) · Florida Department of Environmental Protection (Public Notice of Pollution)
Source: Florida Department of Environmental Protection (Public Notice of Pollution) via Florida DEP Public Notice of Pollution, sewage and wastewater notices (PNP feature service), record 20269950-20261007T224853, reported Oct 7, 2026, 10:48 PM EDT, retrieved 2026-11-05 06:08 UTC · Read the original notice
Current status from this report
Earlier version. A later record from the same source replaces this one. The newest version sets the map status. read the newer version
A report is not a test of the water. See how we assign statuses.
Read the original notice · Report an error
1. Reported wastewater outlet
Operator named in the record: City of Naples Water Reclamation Facility. Outlet: “1400 3rd Ave N Raw Feed Line Break”. Location: 26.15156, -81.78782; location source: given in the source record, accurate to about 15 metres.
Outfall: a pipe or outlet where wastewater enters a water body.
2. Waters named in the notice
The notice names: “Gordon River”. DirtyWaterWatch links this report to Gordon River, FL. Match basis: the water named in the report.
3. Estimated downstream stretch
No downstream estimate is available for this report.
Map sources: water outlines and launches from OpenBoatLaunch and OpenStreetMap contributors (Open Database License); wastewater outlets from EPA and state records; downstream estimates by DirtyWaterWatch using U.S. Geological Survey maps and flow data. Base map: OpenFreeMap and OpenMapTiles.
When it happened and when it was reported
Event and notice times use Eastern Time (EST or EDT). Retrieval times use Coordinated Universal Time (UTC).
- Started
- Ended
- Detail provided by the source
- Times known to the day only
- Reported to the source
- Published
- not given
- Source last updated
- not given
- Last retrieved by DirtyWaterWatch
What and how much
- Type
- Sanitary sewer overflow (SSO): sewage spills from a sewer meant to carry sewage separately from rainwater.
- Status in the record
- Ended (as reported)
- Material
- “untreated wastewater”
- Volume
- 330,000 gallons (estimated)
- Volume as reported
- “330,000 gallons”
Advice from Florida Department of Environmental Protection (Public Notice of Pollution)
This report includes no advice. Check current local health notices.
- Advice period
- This report does not state a period. See the rule DirtyWaterWatch applies and its source.
- Basis
- not stated
Source and versions
- Source
- Florida DEP Public Notice of Pollution, sewage and wastewater notices (PNP feature service)
- Source record number
- 20269950-20261007T224853
- Original notice
- Read the original notice
- Earlier version
- None: this is the first record
- Later versions
- version 2
Record details
| Record identifier | fl-dep-pnp:20269950-20261007T224853 |
|---|---|
| Source identifier | fl-dep-pnp |
| Source record number | 20269950-20261007T224853 |
| Earlier version | Not provided |
| Type | Sanitary sewer overflow (SSO) |
| Status in the report | Ended (as reported) |
| Sewer operator identifier | Not provided |
| Sewer operator | City of Naples Water Reclamation Facility |
| Federal wastewater discharge permit (NPDES) | Not provided |
| Outlet number | Not provided |
| Outlet name | 1400 3rd Ave N Raw Feed Line Break |
| Water named in the report | Gordon River |
| Linked waters | gordon-river-fl |
| How this report was linked to the water | the water named in the report |
| Latitude | 26.152 |
| Longitude | -81.788 |
| Location source | given in the source record |
| Location accuracy, in metres | 15 |
| Started | Oct 7, 2026 (2026-10-07T00:00:00-04:00) |
| Ended | Oct 7, 2026 (2026-10-07T00:00:00-04:00) |
| Detail provided by the source | to the day only |
| Reported to the source | Oct 7, 2026 (2026-10-07T22:48:53-04:00) |
| Published | Not provided |
| Source last updated | Not provided |
| Last retrieved by DirtyWaterWatch | Nov 5, 2026, 1:08 AM EST (2026-11-05T06:08:44Z) |
| Material | untreated wastewater |
| Volume, in gallons | 330,000 |
| Volume as reported | 330,000 gallons |
| How volume was determined | estimated |
| Authority | Florida Department of Environmental Protection (Public Notice of Pollution) |
| Advice | Not provided |
| Advice period, in hours | Not provided |
| Basis of the advice period | Not provided |
| Original notice | https://ags.dep.state.fl.us/arcgis/rest/services/External_Services/PNP/FeatureServer/1/query?where=INCIDENT_NUMBER%3D20269950&outFields=INCIDENT_NUMBER,INCIDENT_NAME,INCIDENT_REPORT,DATE_TIME_OF_REPORT,RELEASE_START_DATE_TIME,RELEASE_ONGOING,RELEASE_END_DATE_TIME,FACILITY_NAME,FACILITY_ADDRESS_LINE_1,FACILITY_ADDRESS_LINE_2,FACILITY_CITY,FACILITY_STATE,FACILITY_ZIP5,AFFECTED_COUNTIES,MIGRATED_OFFSITE,MIGRATED_COUNTIES,LATITUDE,LONGITUDE,DATUM,MAP_SOURCE_SCALE,OBJECTID&returnGeometry=false&f=json |
Original source data
{
"INCIDENT_NUMBER": 20269950,
"INCIDENT_NAME": "1400 3rd Ave N Raw Feed Line Break",
"INCIDENT_REPORT": "Incident Description: On October 7, 2026, a raw wastewater release occurred at the City of Naples Water Reclamation Facility, 1400 3rd Avenue North, Naples, FL 34102 16:45: Release began from the 30-inch raw feed line. Preliminary findings indicate failure of a 2-inch direct tap. 16:52: The operator on duty notified utility management. 17:00 to 17:30: City personnel coordinated the response, and utility management arrived onsite. 17:51: East and West Influent lines were closed, and the spill ceased. The estimated release volume is 330,000 gallons, based on SCADA flow data from 16:45 to 17:51. 18:00: Emergency contractors arrived onsite. The City selected QE for emergency repairs and Earthview for vacuum-truck support at city lift stations and spill recovery. A containment dike was constructed, and City vacuum trucks were deployed to remove wastewater from the plants stormwater swales and ponds. 19:00 to 20:00: Laboratory personnel collected samples at two water-body entry points and two samples from the plant's stormwater ponds. An estimated 1,000 gallons entered Gordon River. The majority of the spill volume was contained onsite within the facilitys stormwater system, consisting of several swales and two ponds. City vacuum trucks have recovered approximately 20,000 gallons from this system to date; with further recovery efforts ongoing. Current status: The spill has ceased. Recovery efforts continue, State watch office has been notified, and emergency repair of the raw feed line remains in progress through contractor QE. Wastewater Type: Untreated Cause: Break-in-Line Spill Volume: 330,000 Volume Recovered: 20,000 Waterbodies Impacted: Y Clean-up Status: In-progress Clean-up Actions: Vacuumed/pump truck, Washed down area, Water samples taken, Raked and disposed of debris Agencies Notified: [removed]",
"DATE_TIME_OF_REPORT": 1791413333000,
"RELEASE_START_DATE_TIME": 1791331200000,
"RELEASE_ONGOING": "N",
"RELEASE_END_DATE_TIME": 1791331200000,
"FACILITY_NAME": "City of Naples Water Reclamation Facility",
"FACILITY_ADDRESS_LINE_1": "1400 3rd Ave N",
"FACILITY_ADDRESS_LINE_2": null,
"FACILITY_CITY": "Naples",
"FACILITY_STATE": "FL",
"FACILITY_ZIP5": 34102,
"AFFECTED_COUNTIES": "Collier",
"MIGRATED_OFFSITE": "Y",
"MIGRATED_COUNTIES": "Collier",
"LATITUDE": 26.151559,
"LONGITUDE": -81.787825,
"DATUM": "WGS84",
"MAP_SOURCE_SCALE": null,
"reached_water": true